Industry

Cummins diesel generator set storage and installation

The storage, installation and use site selection of Cummins diesel generator set shall meet the following conditions:

1. The equipment room is bright and spacious, well ventilated, with low humidity and ambient temperature < 40 ° C.

2. Good lighting equipment should be used for night work, and protective cover should be added for outdoor use to avoid rain and exposure to the sun;

3. The environment should be clean, and articles that produce corrosive gases such as acid and alkali are not allowed around;

4 diesel engine exhaust pipe should be smooth, try to avoid too long pipe or sudden turn. When the exhaust pipe is connected to the outside, it is advisable to tilt the outer pipe down a little to divert the condensate water in the pipe.

5. If the diesel generator set is not fixed on the foundation, rubber plates can be placed under the chassis to reduce vibration;

Cummins diesel generator set installation should do the following:

1. The foundation shall be made of concrete, but shall not be attached to the building foundation. The distance between the building wall and the unit is no less than 1.5 meters;

2. Use a level to measure the levelness during installation to ensure that the unit is fixed at a horizontal position;

3. For personal safety, the generator and switch panel must be separately grounded. The area of ground wire should not be smaller than the cross-sectional area of the generator output line. The ground cable can be connected to underground water pipes or steel plates buried deep underground. Ensure good grounding and grounding resistance shall not be greater than 50 ohms.

4. Open type cooling unit must be equipped with another cooling water pipeline to ensure adequate supply of cooling water;

5. In order to reduce environmental noise, external noise muffler can be connected;

6. After installation, the concentricity of the generator shaft to the main shaft of the diesel engine should generally be less than 0.15mm, and the runout of the generator axis to the flywheel face should generally be less than 0.5/400;

7. The battery should be connected according to the start-up and charging circuit diagram in “Diesel Engine Maintenance and Use Instructions”;

Jiangsu Meiao Power Technology Co., Ltd. is an important manufacturer of diesel generators. Us ao-generator set manufacturers mainly manufacture and sell diesel generator sets, the power of generator sets is 3-3000KW, mobile station is 24-600KW, Marine emergency diesel generator set 24-800KW, gas generator set, heavy oil generator set and all kinds of imported series, special series (trailer, silent speaker, mobile lighthouse, container, etc.) diesel generator Group at the same time engaged in generator set maintenance and generator set accessories after-sales service.